Download

Inverters – Power One PVI-12.0-I


General Description
Small Scale Application Inverter (Isolated), mainly used for 12-13kW residential projects. Its main features are: twin-MPPT design (wide MPPT voltage range), max efficiency at 97.3% and built-in Circuit Breaker for external sound alarming system.
Certificates
UK G83/1, UKG59/2-1, CE, IEC 61727, IEC 62116, EN50178, IEC/EN 62109-1 & IEC/EN62109-2
Specs
DC Input Side Data
Max. PV input power(DC1/DC2) 12300W
Max. PV input voltage 520V
Startup voltage 200V
MPP voltage range for nominal power 250~470V
No. of MPPTs 2
Max. PV input current(DC1/DC2) 50A(25A/ 25A)
AC Output Side Data
Nominal AC output power 12000W
Max. AC output apparent power 12500VA
Max. AC output current 18A
Nominal AC voltage 400Vac (Three phase)
AC voltage range 320~480Vac (The AC voltage range may vary depending on specific country grid standard)
Nominal grid frequency 50Hz/60Hz
THD < 2 % (Nominal power)
DC current injection N.A (Isolated)
Power factor > 0.995 (adj. +/- 0.9)
Protection
Anti-islanding protection Yes
DC reverse connection protection Yes
AC short circuit protection Yes
Leakage current protection Yes